Pneumatic training
Chapter 11 - Valves and Actuators with the NAMUR-interface
Valves with NAMUR-interface to control process valves
1. Pneumatic actuation of process valves
Process valves can be actuated manually, electrically, pneumatically and hydraulically. Often times pneumatic actuators are in use when it comes to automated process valves. They are mostly either linear actuators (pneumatic cylinders) or rotary actuators.
Whether it's a linear or rotary actuator, the pneumatic automation of process valves is popular.
There are distinct advantages of pneumatic actuators in comparison to electric ones:
- High torque
- Low maintenance
- Few spareparts
- High durability
- High reliability
- Usable in explosion hazardous environments
- Economical / cost effective
As the field of applications and types of process valves is extremely wide, we will not cover that.
Instead, we will focus on the pneumatic actuation and control of rotary actuators with NAMUR-interface.
A pneumatically automated process valve has three main parts:
1. Process valve
Part of the pipe-line system, e.g. ball valve or butterfly valve.
2. Pneumatic rotary actuator
Opens and closes the process valve.
3. Pilot valve (with NAMUR-interface)
Directional control valve to control pneumatic rotary actuators.
Further important elements can be:
- Switch-box to feed the position of the process valve back to a central command,
- Manual override – clutch for emergencies or
- Positioner, replacing the switch-box and mostly including the control valve.
2. Pneumatic rotary actuators
The design and dimensions of rotary actuators differ from manufacturer to manufacturer. The two most popular designs are either Scotch-Yoke or Rack and Pinion actuators. We will introduce you to the Rack and Pinion actuator with more detail.
The 2 piston rods of the 2 pistons inside the actuator are shaped like racks. Compressed air is driving them.
The racks drive a pinion which is linked via a shaft to the process valve and opens or closes it

The selected size of the actuator depends on the force required to open and close the process valve. Usually the manufacturer indicates the maximum torque the actuator offers at a specific pressure.
There are two versions of linear actuators:
- Double-acting actuators
- Single-acting actuators (with mechanic spring return)
In double acting actuators - depending on the direction required - compressed air flows to the outside or to the inside of the two pistons. This can be easily controlled by using 5-way directional control valves (5/2-way for fully opening and closing the process valve, 5/3-way if intermediate positions are required).
In single-acting actuators, the reset to basic position is realized by using packs of mechanical springs.
Two packs of springs are positioned on the outside of the actuator, pushing the pistons into the middle position. The area, the springs are in, is called "spring chamber"
As soon as the actuation side of the actuator is exhausted, the springs push the pistons together, which turns the pinion and (depending on the requirement) opens or closes the process valve.
There are standards for the contact interfaces of a rotary actuator, e.g.:
- Contact interface to the control valve | VDI/VDE 3845 (NAMUR)
- Contact interface to the process valve | ISO 5211 | DIN 3337
VDI/VDE 3845 (NAMUR)
Interface on the actuator that allows to flange directly a control valve with NAMUR-interface.
ISO 5211 | DIN 3337
Connection to the process valve.
3. The NAMUR-interface
NAMUR-valves are control valves which offer an assemblage interface according to the standardVDI/VDE 3845.
NAMUR-valves are different from other in-line valves as they offer two ports on the flat side of the valve. In addition, there are holes for fixing the valve onto the actuator.
The drawing below shows a single solenoid 5/2-way valve with an interface according to NAMUR.
Type: MNH 510 701

Besides the 1/4" interface there is also a 1/2" interface for larger actuators:
- G 1/4"-interface NAMUR valve | called: [NAMUR 1/4"] or NAMUR 1
- G 1/2"-interface NAMUR valve | called: [NAMUR 1/2"] or NAMUR 2
|
T |
D1 |
D2 |
M |
NAMUR 1/4" |
G 1/8" / G 1/4" |
32 |
24 |
M 5 |
NAMUR 1/2" |
G 3/8" / G 1/2" |
45 |
40 |
M 6 |
Hole M: typically used for mounting a setscrew onto the rotary cylinder, which fits into the blind bore of the valve and defines its operating direction.
Hole R: used for fastening screws.
The picture displays a MNH 510 701, which is a 5/2-way single solenoid NAMUR-valve. It is used to control a double-acting actuator.
Port 2 and 4 are on the side of the valve. The ports are sealed towards the actuator with O-rings.
Port 1 (=supply) and ports 3 and 5 (=exhausts) are on the flat side of the valve (shown here on the top)

The picture displays a MNH 310 701, which is a 3/2-way single solenoid NAMUR-valve. It is used to control a single-acting actuator.
Port 2 and 3 are on the side of the valve. The ports are sealed towards the actuator with O-rings.
Port 1 (=supply) and the other port 3 (=exhaust) are on the flat side of the valve (shown here on the top)

A normal 3/2-way inline valve has 3 ports. The 3-way NAMUR-valve on the photo however has 4, which you can also see on its ISO symbol. WHY IS THAT?
Single-acting actuators (with springs) have 2 ports. One of the two ports supplies compressed air to the actuation side of the actuator. The other port leads to the spring chamber, which is pressurized and vented through port 3 of the NAMUR-valve.
In order to avoid corrosion of the springs, no air from the atmosphere (which might be wet and polluted" should enter the spring chamber. Instead, (potentially cleaner) process air is fed intro the spring chamber.
That is why in process automation, we aim towards an air recirculation into the spring chamber, also called a "purge".
When the actuation side of the actuator is exhausted (3/2-way valve n.c. in standard postion), the actuation chambers are gradually becoming smaller and the spring chambers larger as the springs expand. The 3/2-way NAMUR-valve feeds part of the process air into the spring chambers before it is used to expand the actuation chambers. The excess air exhausts through the external (second) port 3. This function is indicated in red in the ISO symbol below.

By feeding process air into the spring chambers, we want to reduce pollution inside the actuator due to dirt, dust, mist, moisture etc. that might have been sucked into the spring chambers and thus avoid corrosion of the springs.
4. HAFNER valves with NAMUR-interface
HAFNER Pneumatik offers a uniquely wide range of valves and accessories with NAMUR-interface.
- Solenoid valves | 3/2- (n.c. / n.o.), 5/2- and 5/3-way
- Pneumatically actuated valves | 3/2-, 5/2- and 5/3-way
- Hand lever valves | 3/2-, 5/2- and 5/3-way
- Everything mentioned above both in NAMUR 1 and NAMUR 2
- Numerous products made of stainless steel, for cold and for explosion-hazardous environments
- Flow-regulator plates
- Quick-exhaust valves and "purge-blocks"
- Numerous safety valves (manually, pneumatically or electrically actuated)
- Plates and accessories
Besides standard products, HAFNER Pneumatik also offers:
- NAMUR Flex | 5/2-way valve with a kit to convert it into a 3/2-way valve with air recirculation
- Stainless steel valves | made from 1.4404 (316L)
- Low temperature valves | -50 °C to +50 °C
- High temperature valves | -20 °C to +80 °C
- BSP or NPTported
- ATEX-certified products for explosion-hazardous environment
- Specially selected materials | brass-free products
- Products with air springs or combined springs
- Products with swapped ports
- Products with different types of manual override
Specifications of the standard HAFNER 5/2-way NAMUR-valve type MNH 510 701
- Orrifice size: DN 7 mm
- Air-flow rate: 1,250 l/min
- Operating pressure: 2-10 bar
- Power consumption: 3 W / 5 VA (in combination with standard coil MA 22)
- Ports 1, 2, 3: G 1/4"
- NAMUR: 1/4"

MNH 511 701: same specs, but with a combined mechanical and pneumatic spring return.

Standard sizes of HAFNER NAMUR-valves:
- Series 701 | orifice:7 mm | flow:1,250 l/min | ports:G 1/4" – 1/4" NPT | NAMUR 1, 1/4"
- Series 101 | orifice:10 mm | flow:2,250 l/min | ports:G 3/8" | NAMUR 1, 1/4" maximized air-flow
- Series 121 | orifice:12 mm | flow:3,000 l/min | ports:G 1/2" – 1/2" NPT | NAMUR 2, 1/2"
- Conforming to standards, the flow measurement is shown as nominal flow in [l/min]. Nominal flow: at p1= 6 bar, p = 1 bar, stream-value of the compressed air (l/min).
Besides a maximum flow of 1,250 l/min in a compact design there are 10 more competitive advantages of the Hafner NAMUR valves series 701.
- PA fixing nut, which protects the solenoid system from wetness and moisture.
- Coil MA 22 fully covered with PA or Epoxy (on request), 360° rotatable. Others (Ex-versions) available on request.
- Brass operator tube, including O-ring to protect solenoid system from wetness from the bottom.
- Head made from PA.
- Brass manual override for turning; other versions and materials (e.g. stainless steel) on request.
- Spool made of stainless steel; other inner parts are: brass, POM, NBR, FKM.
- Fixing screws, stainless steel.
- Body, anodized aluminum.
- End-cap made from brass.
- Unique sealing system, the HAFNER swimming O-Ring.
5. Selection of Hafner NAMUR-Accessories
MNH 350 701: HAFNER NAMUR-Flex valve
HAFNER's MNH 350 701, is a single solenoid 5/2-way NAMUR-valve, electrically actuated with air spring return. It is used to control double-acting actuators (with the same function as the MNH 510 701)
This valve is also available in stainless steel and NPT ported.

Adding the Flex-Plate type FP 701, the valve is converted into a 3/2-way NAMUR-valve with air recirculation for the spring chamber (purge).

DRN...: Flow regulator plates
The HAFNER flow regulator plates offer a very precise control of the opening and closing speed of actuators. The regulation is possible with 3-way and 5-way valves.
Additionally, the DRN offers the only possibility to regulate the forward and backward stroke of single-acting actuators independently.
Two different regulation types are available:
- DRN 601: operated manually through a knurled screw
- DRN 611: operated with a screwdriver
Plates are availanle with 1/4" and 1/2" NAMUR-interface.
Assemblage between NAMUR pilot-valve and actuator or with threaded plate type GPN 1/4" for direct piping.
UB 701: NAMUR Air-recirculation block
The air‑recirculation block ensures that only exhaust air from the actuation chamber enters the spring chamber, preventing any ambient air from being drawn in. It is used with single‑acting actuators controlled by remotely installed 3/2‑way valves, e.g. from a control cabinet.
- DRN 601: operated manually through a knurled screw
- DRN 611: operated with a screwdriver
Plates are available with 1/4" and 1/2" NAMUR-interface.
Assemblage between NAMUR pilot-valve and actuator or with threaded plate type GPN 1/4" for direct piping.
More information about NAMUR-valves and accessories can be found in our valve catalog section 2.10 NAMUR-valves.